Updated September 2026: current BACnet/IP F332 Smart Actuator range, communication details and 2026 technical literature.
The SAUTER Smart Actuator range combines actuation, freely programmable local control and connected building-automation integration within one device. The range covers ball valves, linear 2- and 3-way valves and ventilation dampers, allowing the actuator to perform autonomous or semi-autonomous HVAC control while exchanging information with the wider BMS.
The current F332 models provide BACnet/IP communication over Ethernet or Wi-Fi. They can be commissioned and parameterised through the SAUTER mobile app or SAUTER CASE engineering software and can connect to the SAUTER Cloud through MQTT with TLS encryption where the project architecture requires cloud-based access.

Select the Smart Actuator by Mechanical Duty
The three Smart Actuator families share a common control and communications platform but perform different mechanical duties. Selection must begin with the valve or damper application rather than the communication protocol alone.
| Model | Control duty | Mechanical output | Connectivity and I/O |
|---|---|---|---|
| AKM115SAF332 | Ball valves, including compatible six-way ball valves | 8 Nm rotary actuator; 90° rotation | BACnet/IP via Ethernet or Wi-Fi; Bluetooth LE; two universal I/Os |
| AVM115SAF332 | Compatible two- and three-way valves | 250 N actuating force, configurable to 500 N; 0–10 mm stroke | BACnet/IP via Ethernet or Wi-Fi; Bluetooth LE; two universal I/Os |
| ASM115SAF332 | Round and rectangular ventilation dampers | 10 Nm rotary actuator; maximum 95° rotation | BACnet/IP via Ethernet or Wi-Fi; Bluetooth LE; two universal I/Os |
Shared F332 Control and Communication Functions
The AKM, AVM and ASM F332 Smart Actuators share the following control and integration capabilities:
- 24 VAC or 24 VDC power supply
- Maximum 5 W/10 VA power consumption without connected peripheral devices
- BACnet/IP communication over Ethernet or Wi-Fi
- Integrated Ethernet switch with two RJ45 connections
- HTTPS, NTP and DHCP support
- Bluetooth LE for local device communication
- Two universal I/Os for compatible external sensors and actuators
- Up to 100 BACnet data-point objects and 16 BACnet client links
- Six control loops, four time programmes and three calendars
- Real-time clock for time programmes and calendar functions
- SLC master connection for compatible SAIO 100, ecoLink and room-operating peripherals
- Application engineering through SAUTER CASE Suite or the mobile-app workflow
- MQTT cloud communication using TLS encryption
The precise peripheral arrangement, power requirements and SLC device limits must be checked against the applicable product data sheet. Cables and other accessories are ordered separately.
BACnet/IP and BACnet MS/TP Variants
The three 2026 product data sheets linked on this page cover the F332 BACnet/IP models. BACnet/IP communication is provided through the Ethernet or Wi-Fi interface. The RS-485 connection on these F332 models operates as an SLC master for compatible SAUTER peripheral devices; it is not the BACnet MS/TP connection.
The wider 2026 SAUTER Valves & Actuators Catalogue also identifies F232 Smart Actuator variants with BACnet MS/TP communication. The full model reference and communication suffix must therefore be confirmed against the project network architecture before ordering.
HVAC Applications
The Smart Actuator can carry out local control tasks without requiring a separate automation station for every application. SAUTER provides ready-made HVAC applications through its application library, while freely programmable applications can be engineered through CASE Suite.
Potential applications include:
- Fan coil and repeated room-control installations
- Heating and cooling coil control
- Heated and chilled ceiling control
- Supply-temperature control
- Plate heat-exchanger control
- Hot- and cold-water storage control
- 2-, 3- and 6-way ball-valve applications
- Ventilation and air-damper control
The availability of a suitable standard application must be checked against the current SAUTER application library. Bespoke sequences, connected field devices, valve or damper selection and supervisory BMS responsibilities must still be engineered for the project.
BMS Integration Responsibilities
Decentralised control should not mean isolated control. The system design must establish which functions are performed by the Smart Actuator and which remain within the supervisory BMS.
The integration design should confirm:
- Local control sequences and operating modes
- Occupied and unoccupied commands
- Setpoints, adjustments and operator overrides
- Alarm, trend and monitoring requirements
- Behaviour following network interruption
- BACnet object and client-link requirements
- Responsibility for application engineering, workshop testing and site commissioning
BACnet connectivity provides the communication interface. It does not establish valve suitability, control sequencing or unrestricted compatibility with every BMS.
Installation and Commissioning
Pre-assembled cables with mechanically and colour-coded connectors are intended to reduce connection errors and support repeatable assembly. The actuator families use mounting arrangements suited to their respective ball-valve, linear-valve or damper applications, with automatic stroke or angle adaptation available where specified.
Applications can be selected and installed through the mobile-app workflow, while commissioning, parameterisation and application engineering can also be undertaken using SAUTER CASE tools.
Smart Actuator Commissioning Video
This quick-start video outlines the principal steps for setting up and commissioning a SAUTER Smart Actuator. It covers the demonstration’s hydraulic and control arrangement, installation of the Smart Actuator app, SAUTER Cloud registration, application selection, device connection, parameter configuration and remote access.
Watch the SAUTER Smart Actuator commissioning video on YouTube.
For repeated room or fan-coil installations, the control assembly can be configured and tested before delivery to site. Final installation, network integration, functional checks and system-level commissioning remain project requirements.
IBC’s hotel refurbishment article examines how this approach was applied across 192 rooms:
Read the Fan Coil Control ArticleSystem Expansion and Accessories
Compatible supporting components include the SAIO100F020 I/O module, SAUTER room operating units, ecoLink modules, power supplies, pre-assembled cables, connector protection sets and product-specific valve or mounting adaptors.
SAIO100F020 I/O Module
Where additional field connections are required, the SAUTER SAIO100F020 extends the Smart Actuator system with five universal I/O channels and three changeover relay outputs. It connects to the Smart Actuator through SLC and supports a separate 24 V supply for connected sensors and actuators. Up to two SAIO100 modules can be connected to one Smart Actuator, subject to the applicable power requirements and SLC device limits.
View the SAUTER SAIO100F020 I/O module and access technical downloads.
Power and Connecting Cables
SAUTER provides power-supply and connecting cables for linking Smart Actuators with sensors, peripheral devices and SAIO I/O modules. The required cable configuration and length should be selected according to the connection and installation arrangement. Cables and other accessories are ordered separately.
View SAUTER Smart Actuator power and connecting cable technical data (PDF).
SAUTER Smart Actuator Technical Downloads
Supply and Application Support
IBC supplies SAUTER Smart Actuators and compatible valves, room operating units, I/O modules, cables and accessories. Product availability and final selection depend on the mechanical application, required control sequence, connected devices and project network architecture.
Contact IBC to discuss Smart Actuator selection, system integration or project pricing.
Contact IBC