Touch Point ONE 2.0 Room Automation Interface
Touch Point ONE 2.0 combines HVAC comfort control, environmental sensing, lighting commands and blind commands within one glass-fronted room interface. It is designed for integrated room automation applications that would otherwise require several separate wall devices.
The panel communicates with a compatible controller over RS485 using BACnet MS/TP or Modbus RTU/ASCII. Occupant commands and measured values are passed to the controller, where the HVAC, lighting and blind-control logic and field outputs are managed.
Key Features
- Combined HVAC, lighting and blind room interface
- Standard, two-light and one-blind control layouts
- 0.96-inch TFT display
- Occupancy, temperature setpoint and fan-control functions
- Temperature sensor fitted as standard
- Optional relative humidity and CO2 sensing
- BACnet MS/TP and Modbus RTU/ASCII communication
- Two Smart Plug™ RJ45 connectors combining power and RS485
- Removable screw terminal for direct power and RS485 connection
- RJ45 daisy-chain support
- USB-C connection for local configuration
- Free iSMA Configurator software
- Configurable RGB navigation LED
- Black or pure white glass front
- Suitable for a standard 60 mm wall back box
Three Room-Control Layouts
| Layout | HVAC functions | Lighting and blind functions |
|---|---|---|
| TP-ONE | Occupancy, temperature setpoint and fan control | Supports commands for up to four lighting circuits and four blinds |
| TP-ONE-2L | Occupancy, temperature setpoint and fan control | Dedicated control of two lighting circuits, including on/off and dimming commands |
| TP-ONE-1B | Occupancy, temperature setpoint and fan control | Dedicated control of one blind |
The standard TP-ONE layout is designed for nano EDGE ENGINE controllers and requires the dedicated TpOneControlLogic component. The two-light and one-blind layouts provide generic button states that can be assigned to the required functions within the controller application.
Touch Point ONE 2.0 Model Selection
| Control layout | Sensor configuration | Black model | White model |
|---|---|---|---|
| TP-ONE | Temperature | TP-ONE-DISP-B-2 | TP-ONE-DISP-W-2 |
| TP-ONE | Temperature + CO2 | TP-ONE-C-DISP-B-2 | TP-ONE-C-DISP-W-2 |
| TP-ONE | Temperature + relative humidity | TP-ONE-H-DISP-B-2 | TP-ONE-H-DISP-W-2 |
| TP-ONE | Temperature + relative humidity + CO2 | TP-ONE-HC-DISP-B-2 | TP-ONE-HC-DISP-W-2 |
| TP-ONE-2L | Temperature | TP-ONE-DISP-2L-B-2 | TP-ONE-DISP-2L-W-2 |
| TP-ONE-2L | Temperature + CO2 | TP-ONE-C-DISP-2L-B-2 | TP-ONE-C-DISP-2L-W-2 |
| TP-ONE-2L | Temperature + relative humidity | TP-ONE-H-DISP-2L-B-2 | TP-ONE-H-DISP-2L-W-2 |
| TP-ONE-2L | Temperature + relative humidity + CO2 | TP-ONE-HC-DISP-2L-B-2 | TP-ONE-HC-DISP-2L-W-2 |
| TP-ONE-1B | Temperature | TP-ONE-DISP-1B-B-2 | TP-ONE-DISP-1B-W-2 |
| TP-ONE-1B | Temperature + CO2 | TP-ONE-C-DISP-1B-B-2 | TP-ONE-C-DISP-1B-W-2 |
| TP-ONE-1B | Temperature + relative humidity | TP-ONE-H-DISP-1B-B-2 | TP-ONE-H-DISP-1B-W-2 |
| TP-ONE-1B | Temperature + relative humidity + CO2 | TP-ONE-HC-DISP-1B-B-2 | TP-ONE-HC-DISP-1B-W-2 |
Environmental Sensing
Every Touch Point ONE 2.0 model includes temperature sensing. Additional models incorporate relative humidity, CO2, or combined humidity and CO2 measurement for use within the connected room-control application.
CO2-equipped models also support configurable high-CO2 alarm functionality.
Smart Plug™ Installation
Two Smart Plug™ RJ45 ports combine 24 V power and RS485 communication in one connection. This supports faster installation and straightforward daisy-chaining between compatible Touch Point 2.0 devices.
A removable screw terminal is also provided for direct power and RS485 wiring where RJ45 connectivity is not required.
Communication and Configuration
BACnet MS/TP or Modbus RTU/ASCII communication is selected using the onboard DIP switch. The RS485 interface supports baud rates from 2400 to 115200 and networks containing up to 128 devices.
The interface can be configured locally through its USB-C connection using the free iSMA Configurator, or through Modbus registers and BACnet objects.
Technical Specifications
| Power supply | 20–40 V DC or 24 V AC ±20% |
|---|---|
| Power consumption | 0.6 W at 24 V DC or 1.9 VA at 24 V AC |
| Display | 0.96-inch TFT |
| Buttons | 7 |
| Button backlight | Three intensity modes |
| Temperature sensor | 10k NTC, 0–50°C range, ±0.5°C accuracy and 0.1°C resolution |
| Humidity sensor | 0–100% RH range, ±2% RH accuracy between 10% and 90% RH |
| CO2 sensor | 400–2000 ppm range, accuracy of ±(50 ppm + 5% of reading) |
| Communication | BACnet MS/TP or Modbus RTU/ASCII over RS485 |
| RS485 capacity | Up to 128 devices, half-duplex |
| Connections | Two Smart Plug™ RJ45 ports, removable screw terminal and USB-C |
| Operating temperature | 0°C to +40°C |
| Dimensions | 86 × 86 × 14.8 mm |
| Ingress protection | IP20 for indoor installation |
Complete Zone Control with ZAC24-IP-D
Touch Point ONE 2.0 is a particularly strong room-side pairing for the ZAC24-IP-D zone application controller. The panel provides occupants with one interface for comfort, lighting and blind commands, while the controller manages the HVAC, DALI-2 lighting and blind-control application.
The manufacturer’s application example also shows Touch Point ONE 2.0 communicating with RAC18-IP and UAC28-IP controllers over Modbus RTU or BACnet MS/TP. The required controller, software components and control layout should be confirmed during model selection.
Technical Literature
The shared Touch Point 2.0 hardware and software user manuals are available from the Touch Point 2.0 family page.
Explore the Touch Point 2.0 Range
This is the all-in-one interface for combined HVAC comfort, lighting and blind commands. For standard HVAC control, VAV applications, distributed environmental sensing, or a dedicated lighting and blind interface, explore the complete Touch Point 2.0 range.
Available Through IBC
For control-layout selection, sensor options, controller pairing, availability or project pricing, contact IBC.