Touch Point Network Sensor 2.0 for Distributed Room Sensing
The Touch Point Network Sensor 2.0 is a wall-mounted network multisensor for applications requiring environmental measurements without a display or local control buttons.
Temperature sensing is included as standard, with model options adding relative humidity, CO2, or both. Measurements are communicated over RS485 to a compatible zone controller or BMS master using BACnet MS/TP or Modbus RTU/ASCII.
Key Features
- Integrated temperature sensor across every model
- Optional relative humidity and CO2 sensing
- No display or occupant-control buttons
- One freely configurable RGB status LED
- BACnet MS/TP and Modbus RTU/ASCII communication
- Two Smart Plug™ RJ45 connectors combining power and RS485
- Removable screw terminal for direct power and RS485 connection
- RJ45 daisy-chain support for flexible installation
- USB-C connection for local configuration
- Free iSMA Configurator software
- Black or pure white glass front
- Suitable for a standard 60 mm wall back box
Touch Point Network Sensor 2.0 Model Selection
| Sensor configuration | Black model | White model |
|---|---|---|
| Temperature | TP-NS-B-2 | TP-NS-W-2 |
| Temperature + CO2 | TP-NS-C-B-2 | TP-NS-C-W-2 |
| Temperature + relative humidity | TP-NS-H-B-2 | TP-NS-H-W-2 |
| Temperature + relative humidity + CO2 | TP-NS-HC-B-2 | TP-NS-HC-W-2 |
Smart Plug™ Installation
Two Smart Plug™ RJ45 ports combine 24 V power and RS485 communication in one connection. This supports faster installation and straightforward daisy-chaining between compatible Touch Point 2.0 devices.
A removable screw terminal is also provided for direct power and RS485 wiring where RJ45 connectivity is not required.
Communication and Configuration
BACnet MS/TP or Modbus RTU/ASCII communication is selected using the onboard DIP switch. The RS485 interface supports baud rates from 2400 to 115200 and networks containing up to 128 devices.
The sensor can be configured locally through its USB-C connection using the free iSMA Configurator, or remotely through Modbus registers and BACnet objects.
Technical Specifications
| Power supply | 20–40 V DC or 24 V AC ±20% |
|---|---|
| Power consumption | 0.44 W at 24 V DC or 1.55 VA at 24 V AC |
| Temperature sensor | 10k NTC, 0–50°C range, ±0.5°C accuracy and 0.1°C resolution |
| Humidity sensor | 0–100% RH range, ±2% RH accuracy between 10% and 90% RH |
| CO2 sensor | 400–2000 ppm range, accuracy of 50 ppm + 5% of reading |
| Communication | BACnet MS/TP or Modbus RTU/ASCII over RS485 |
| Connections | Two Smart Plug™ RJ45 ports, removable screw terminal and USB-C |
| Front indication | One configurable RGB LED |
| Operating temperature | 0°C to +40°C |
| Dimensions | 86 × 86 × 14.8 mm |
| Ingress protection | IP20 for indoor installation |
Controller and BMS Integration
The Touch Point Network Sensor 2.0 provides additional networked measurement points wherever local environmental data is required without another occupant interface. It can support distributed sensing across larger, subdivided or differently occupied spaces.
The manufacturer’s application example shows the Network Sensor communicating over Modbus RTU or BACnet MS/TP with compatible zone controllers, including RAC18-IP and ZAC24-IP-D.
Technical Literature
The shared Touch Point 2.0 hardware and software user manuals are available from the Touch Point 2.0 family page.
Explore the Touch Point 2.0 Range
This is the display-free model for distributed temperature, humidity and CO2 sensing. For standard HVAC comfort control, VAV applications, combined room automation, or dedicated lighting and blind control, explore the complete Touch Point 2.0 range.
Available Through IBC