Room Sensing and Occupant Control in One Open-Protocol Interface
A room interface must be straightforward for occupants while providing the BMS with reliable room values and clearly defined user commands. Touch Point 2.0 combines local temperature display, setpoint adjustment, occupancy control and fan selection in one glass-fronted wall unit.
The room unit communicates measured values and occupant commands to the connected HVAC controller or BMS over BACnet MS/TP or Modbus RTU/ASCII. Control logic and field outputs remain within the connected controller, allowing Touch Point 2.0 to provide the room-side interface without duplicating the application controller.
Typical Applications
- Fan-coil unit applications requiring local fan selection
- Heating and cooling zones with occupant setpoint adjustment
- Commercial offices, hotel guestrooms and similar comfort-controlled spaces
- Projects requiring temperature, humidity or CO2 measurement at room level
- New installations and extensions of compatible Touch Point systems
Local Controls and Indication
The capacitive touch interface provides five dedicated controls:
- One occupancy-control button
- Two buttons for increasing or decreasing the temperature setpoint
- Two buttons for selecting the fan operating mode
The fan interface supports off, three manual fan speeds and automatic operation, subject to the connected controller application. The display can show the current room temperature, temperature setpoint or offset and, on applicable models, relative humidity and CO2.
LED indication provides feedback for temperature adjustment, fan mode, occupancy and ECO status. A configurable RGB navigation LED can help locate the panel in low-light conditions. Audible touch feedback is also provided, while CO2-equipped models support a configurable high-level alarm.
Model Selection
Every Touch Point 2.0 Room Operating Unit includes temperature sensing and a display. Humidity and CO2 options can be selected in either a black or white glass finish.
| Sensor configuration | Black model | White model |
|---|---|---|
| Temperature | TP-DISP-B-2 | TP-DISP-W-2 |
| Temperature and humidity | TP-H-DISP-B-2 | TP-H-DISP-W-2 |
| Temperature and CO2 | TP-C-DISP-B-2 | TP-C-DISP-W-2 |
| Temperature, humidity and CO2 | TP-HC-DISP-B-2 | TP-HC-DISP-W-2 |
Built-in Sensor Performance
| Measurement | Range | Accuracy |
|---|---|---|
| Temperature | 0 to 50°C | ±0.5°C |
| Relative humidity | 0 to 100% RH | ±2% RH from 10 to 90% RH |
| CO2 | 400 to 2,000 ppm | ±(50 ppm + 5% of reading) |
CO2 application note: The CO2 sensor uses automatic self-calibration and assumes periodic exposure to a fresh-air baseline. Suitability should be confirmed for spaces that remain continuously occupied or at elevated CO2 levels.
Smart Plug™ Wiring and Daisy-Chain Expansion
Two Smart Plug™ RJ45 connections combine RS485 communication and power in one cable. This allows the panel to be powered directly from a compatible controller and supports daisy-chaining to additional room devices.
A removable screw connector provides an alternative connection for power and RS485 communication. Although Smart Plug™ uses RJ45 connectors, these carry serial communication and power rather than Ethernet.
Configuration and BMS Integration
Modbus RTU/ASCII or BACnet MS/TP operation is selected using a DIP switch on the rear of the panel. The same switch assembly provides factory-reset and 120 Ω RS485 termination functions. A rotary switch supports quick Modbus address selection from 0 to 9, with wider addressing available through the device parameters.
Configuration and firmware updates can be completed through the USB-C port using the free iSMA Configurator. Operating parameters are also accessible through Modbus registers or BACnet objects.
Touch Point 2.0 is a configurable room operating unit rather than a freely programmable controller. HVAC control logic, sequencing and physical outputs are managed by the connected application controller.
Technical Specifications
| Power supply | 20–40 V DC or 24 V AC ±20% |
|---|---|
| Power consumption | Up to 0.6 W at 24 V DC; up to 1.9 VA at 24 V AC |
| Communication | BACnet MS/TP or Modbus RTU/ASCII over half-duplex RS485 |
| RS485 capacity | Up to 128 devices |
| Baud rate | 2,400–115,200 |
| Connections | Two Smart Plug™ RJ45 ports and removable screw terminals |
| Configuration port | USB-C |
| Display | 0.96-inch TFT with three backlight-intensity modes |
| Controls | Five capacitive touch buttons |
| Front finish | Black or white glass |
| Dimensions | 86 × 86 × 14.8 mm |
| Mounting | Standard 60 mm wall back box or US 1-gang box |
| Ingress protection | IP20 for indoor installation |
| Operating temperature | 0 to 40°C |
| Operating humidity | 5 to 95% RH, non-condensing |
Controller Integration
The Touch Point 2.0 datasheet illustrates integration with iSMA CONTROLLI RAC18-IP, ZAC24-IP-D and UAC28-IP controllers. The appropriate controller, application and communication settings should be selected around the required room-control strategy.
Replacing or Extending an Existing Touch Point Installation?
Selected configurations from the previous Touch Point range are carried forward within the Touch Point 2.0 basic line. However, previous-generation and Touch Point 2.0 product codes should not be treated as automatic one-for-one replacements.
IBC can confirm the appropriate model for a new installation, project extension or replacement requirement.
Technical Literature
The shared hardware and software user manuals for the complete family are available on the Touch Point 2.0 range page.
Explore the Touch Point 2.0 Range
This is the standard HVAC comfort-control model with dedicated fan buttons. For VAV applications, distributed sensing, combined HVAC and room automation, or dedicated lighting and blind control, explore the complete Touch Point 2.0 range.
For model selection, controller pairing, availability or project pricing, contact IBC.