Merlin 3000S Demand Controlled Kitchen Ventilation
The Merlin 3000S combines automatic ventilation control, gas interlocking and optional gas pressure proving in one commercial kitchen control panel. Two 0–10 V DC outputs regulate compatible extract and supply fan speed controllers, allowing ventilation to respond to sensed kitchen demand.
The system is suitable for new installations and retrofit projects with compatible fan controls. During quieter cooking periods, reduced fan speeds can lower fan electricity consumption and the amount of conditioned air removed through extraction.
System Components
The Merlin 3000S system combines a central control panel with separately selected sensors and ancillary components. The main components illustrated in the product leaflet are shown below. IBC can confirm the components and quantities required for each project.
| Component | Function |
|---|---|
| Merlin 3000S control panel | Controls ventilation demand and gas interlocking. |
| S&S Northern CO₂ iS Detector | Measures CO₂ levels and provides a demand signal to the controller. |
| 2-wire PT100 RTD temperature probes | Measure extract duct temperature for temperature-based ventilation control. |
Additional sensing and ancillary components are selected according to the required system configuration.
How the Ventilation Responds to Kitchen Demand
The Merlin 3000S accepts four types of demand input. Operation depends on the sensors installed and the commissioned settings. S&S Northern recommends using all sensing elements together for the most complete response.
| Demand input | Control function |
|---|---|
| CO₂ monitoring | Accepts 0–10 V signals from compatible CO₂ monitors to adjust ventilation as CO₂ levels change. |
| Real-time gas consumption | Uses a compatible gas meter pulse signal to vary ventilation according to gas usage. |
| Canopy smoke and steam | Optical sensors detect smoke or steam and increase ventilation when required. |
| Extract duct temperature | Temperature probes increase ventilation in response to rising duct temperature. |
The controller supports two sensing zones, allowing monitoring of up to two kitchen canopies. The connected fan speed controllers or inverters must accept a 0–10 V DC control signal.
Gas Interlocking and Optional Gas Proving
The panel interlocks the gas solenoid valve with ventilation status using external fan current monitors or air pressure differential switches. Optional gas pressure proving requires a separately supplied pressure transducer and configuration of the fill and prove times.
Connections are provided for a compatible carbon monoxide detector, CO₂ alarm contact, fire alarm and remote emergency stop devices. These safety inputs operate alongside the demand control functions. Fan responses to fire alarm and emergency stop activation are configurable to suit the specified shutdown sequence.
BMS Interface and Operating Controls
A volt-free changeover output provides a BMS interface. The output can be configured to indicate gas valve status or system faults, allowing the building management system to monitor the selected condition.
- Separate extract and supply fan enable connections.
- Adjustable minimum extract and supply fan speeds.
- Timed fan boost and configurable fan overrun.
- Configurable solid fuel protection function.
- 4.3-inch TFT display with operating, warning and fault indications.
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer / model | S&S Northern / Merlin 3000S |
| Power supply | 100–240 V AC, 50/60 Hz |
| Maximum power consumption | 6.9 W |
| Fan speed control | Two 0–10 V DC outputs: extract and supply |
| Ventilation interlock inputs | External current monitors or air pressure differential switches |
| BMS interface | Volt-free changeover contact; selectable gas valve status or fault indication |
| Gas pressure proving | Optional; separate pressure transducer required |
| Mounting | Indoor wall mounting |
| Dimensions (H × W × D) | 180 × 255 × 77 mm |
Measured Energy Savings: Cambridge Case Study
The product leaflet includes a 2023 Cambridge commercial kitchen case study based on 12 months of recorded data. With demand control applied to the extract fan only, the site recorded annualised electricity savings of 6,675 kWh and an average load reduction of 39.1%.
These results relate to that installation. Project savings depend on operating hours, cooking demand, existing fan operation and the control arrangement installed.
Selection and Commissioning
For a new or retrofit application, the selection should establish fan control compatibility, the required sensing arrangement, ventilation proving method, gas proving requirements and the fire alarm shutdown sequence. Sensors, pressure transducers, fan speed controllers and other ancillary components should be confirmed as part of the project specification.
Technical Downloads
- Merlin 3000S Datasheet & Installation and Operation Manual (PDF) – wiring, configuration, operating sequences, fault indications and technical specifications.
- Merlin 3000S Product Leaflet (PDF) – system overview, inputs and outputs, and Cambridge energy savings case study.