CO₂ iS Detector for Carbon Dioxide Monitoring and Ventilation Control
The S&S Northern Merlin CO₂ iS detector combines carbon dioxide measurement, a local TFT display and analogue and relay outputs. It supports applications requiring a visible CO₂ reading alongside signals for a compatible Merlin panel, building management system or ventilation controller.
The NDIR sensor measures CO₂ concentrations from 0 to 5,000 ppm. The display shows the measured level, while green, amber and red status indication identifies normal, pre-alarm and alarm conditions.
0–10 V Output and BMS Connections
The detector provides a 0–10 V analogue signal proportional to the measured CO₂ concentration. Its output scaling can be selected for either 0–2,000 ppm or 0–5,000 ppm, allowing the signal to be matched to the receiving controller.
Volt-free relay outputs provide pre-alarm and alarm signals for connected equipment. Relay latching and the audible buzzer are configurable. During commissioning, the selected output scaling and alarm settings should be checked against the required control sequence.
Used with the Merlin 3000S
Merlin 3000S Demand Controlled Kitchen Ventilation System
The CO₂ iS detector is one of the sensing components used with the Merlin 3000S commercial kitchen ventilation system. Its 0–10 V signal connects to a CO₂ zone input on the controller, allowing ventilation to respond to changing carbon dioxide levels.
The Merlin 3000S combines the connected demand signals with extract and supply fan control, gas interlocking and optional gas pressure proving. The CO₂ detector, temperature probes and other ancillary components are selected separately to suit the installation.
View the Merlin 3000S system and its components
Configurable CO₂ Alarm Levels
Board-mounted selection switches provide the following pre-alarm and main alarm combinations. The factory setting is 2,800 ppm pre-alarm and 4,500 ppm main alarm.
| Pre-alarm | Main alarm |
|---|---|
| 800 ppm | 1,000 ppm |
| 1,200 ppm | 1,500 ppm |
| 1,500 ppm | 2,800 ppm |
| 2,800 ppm — factory setting | 4,500 ppm — factory setting |
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer / model | S&S Northern / Merlin Detector i-S, CO₂ version |
| Sensing technology | NDIR with ABC automatic calibration |
| Measuring range | 0–5,000 ppm CO₂ |
| Analogue output | 0–10 V; selectable 0–2,000 or 0–5,000 ppm scaling |
| Relay contact rating | 1 A resistive load at 24 V AC/DC |
| Power supply | 12–24 V DC or 24 V AC |
| Display | 1.8-inch TFT with CO₂ reading and status indication |
| Operating conditions | −10 to +50°C; 20–90% RH, non-condensing |
| Mounting | Indoor wall mounting in a safe area |
| Dimensions (H × W × D) | 151 × 111 × 50 mm |
Installation and Commissioning
The detector is supplied factory calibrated. Installation should allow representative CO₂ measurement and access for servicing. Commissioning should verify the detector response, analogue signal scaling, relay operation and the response of the connected control system.
Technical Download
CO₂ iS Installation, Operation & Maintenance Manual (PDF) – mounting, wiring, output scaling, alarm settings, maintenance and technical specifications.