- Performance:
- Accuracy: ±1.0% of reading from 2 – 20 ft/s, ±0.02 ft/s below 2 ft/s.
- Flow Range: 0.1 ft/s to 20 ft/s (200:1 turndown).
- Sensing Method: Electromagnetic sensing (no moving parts).
- Operating Conditions:
- Minimum Conductivity: 25 μS/cm.
- Fluid Temperature Range: 15°F to 250°F.
- Fluid Pressure Range: 400 psi maximum.
- Ambient Conditions: Board: -20°F to 150°F.
- Pressure Drop:
- Standard Configuration: 0.1 psi at 12 ft/s in 3” pipe, decreasing as line size increases.
- Small Pipe Configuration: 0.33 psi at 8 ft/s in 1.25” pipe, decreasing as the line size increases.
- Pipe Size Range:
- Standard Configuration: 3” – 72” nominal diameter (1.25” to 2.5” coming in Q2 2024).
- Input Power:
- 22 – 26 VDC with maximum power draw at 25 Watts.
- 20 – 28 VAC with maximum power draw at 30 VA, 60 Hz.
- I/O Signals:
- Two (2) Analog Outputs: Active 4-20mA, 0-10V, or 0-5V.
- Two (2) Analog Inputs: Passive 4-20mA.
- Two (2) 1000ohms RTD Inputs.
- Three (3) Digital Inputs/Outputs (Field Selectable).
- One (1) Frequency Output: 0-15V peak pulse, 0-1000hz.
- Electronic Enclosure:
- Flow Sensor Rating: NEMA 6.
- Remote Mount Display Rating: NEMA 4.
- Mounting Option: Remote mount with kit, up to 200ft.
- Display: 4.3 inch touch screen display. Resolution of 480×272 pixels.
- Material:
- Remote Mount Display: Powder Coated Die Cast Aluminum.
- Flow Sensor: Wetted metal components: 316 Stainless Steel, Sensor head: XAREC.
- Factory Provided Cable (Sensor to Remote Display): Up to 200’ of three twisted pairs, 22 gauge conductors with individual shields, PVC jacketed, suitable for direct burial with ½” NPT conduit connections or strain relief fitting.
- Programming:
- Available Options: Menu-driven user interface via touchscreen, PC user interface via micro USB and downloadable software.
- Electrical Connections:
- Input Power: Removable orange terminal blocks for use with 18-22 AWG.
- I/O Signals: Removable green terminal blocks for use with 18-22 AWG.
- RS485: Removable green terminal blocks for use with 18-22 AWG.
- IP: RJ45 connector.
- Communication Protocols:
- BACnet MS/TP, BACnet UDP/IP, MODBUS RTU, MODBUS TCP/IP.
- Network Configuration & Addressing:
- BACnet MS/TP: Baud Rates: 9600, 19200, 38400, 57600, or 76800 (Default: 38400), Device Address Range: 1 – 127 (Default: 017), Device Instance Range: 1 – 4,194,302 (Default: 57017), Max master: 1-127.
- BACnet UDP/IP: IPV4 Address: Programmable (Default: 192.168.1.24), Instance Number: 1 – 4,194,302 (Default: 57017), Subnet Mask: Programmable (Default: 255.255.255.0), Gateway Address: Programmable, UDP port: Programmable (Default: 47808).
- MODBUS RTU: MODBUS Address Range: 1- 247 (Default: 017), Baud Rates: 9600, 19200, 38400, 57600, or 76800 (Default: 38400), Data format: 8 bit, Stop bits: 1, Parity: None, Odd, or Even (Default: None), Byte Order: ABCD.
- MODBUS TCP/IP: IPV4 Address: Programmable (Default: 192.168.1.24), Subnet Mask: Programmable (Default: 255.255.255.0), Gateway Address: Programmable, Port: Programmable (Default: 502).
- Approvals:
- CE: IEC 61000-6-2 Power-Frequency Magnetic Field, Radiated Immunity and Electrostatic Discharge, IEC 61000-6-4 Radiated Emissions, EN 301 489-17 Radiated Emission, RF Immunity, and Electrostatic Discharge, EN 301 328 Wideband transmission systems.
- UL: UL 50: Standard for Enclosures for Electrical Equipment, UL ANSI/NSF 61 & 372 Drinking Water Safety (SENSOR ONLY), UL 61010-1 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use.
- FCC: Part 15, Subpart B.