FT-3500 ONICON Insertion Electromagnetic Flow Meter

Enquire Now

Tech specs:

 

  • Performance:
    • Accuracy: ±1.0% of reading from 2 – 20 ft/s, ±0.02 ft/s below 2 ft/s. ​​
    • Flow Range: 0.1 ft/s to 20 ft/s (200:1 turndown). ​
    • Sensing Method: Electromagnetic sensing (no moving parts). ​
  • Operating Conditions:
    • Minimum Conductivity: 25 μS/cm. ​
    • Fluid Temperature Range: 15°F to 250°F. ​
    • Fluid Pressure Range: 400 psi maximum. ​
    • Ambient Conditions: Board: -20°F to 150°F. ​​
  • Pressure Drop:
    • Standard Configuration: 0.1 psi at 12 ft/s in 3” pipe, decreasing as line size increases. ​​
    • Small Pipe Configuration: 0.33 psi at 8 ft/s in 1.25” pipe, decreasing as the line size increases. ​
  • Pipe Size Range: ​​
    • Standard Configuration: 3” – 72” nominal diameter (1.25” to 2.5” coming in Q2 2024). ​​
  • Input Power:
    • 22 – 26 VDC with maximum power draw at 25 Watts. ​
    • 20 – 28 VAC with maximum power draw at 30 VA, 60 Hz. ​
  • I/O Signals:
    • Two (2) Analog Outputs: Active 4-20mA, 0-10V, or 0-5V. ​
    • Two (2) Analog Inputs: Passive 4-20mA. ​​
    • Two (2) 1000ohms RTD Inputs. ​
    • Three (3) Digital Inputs/Outputs (Field Selectable). ​
    • One (1) Frequency Output: 0-15V peak pulse, 0-1000hz. ​
  • Electronic Enclosure:
    • Flow Sensor Rating: NEMA 6. ​​
    • Remote Mount Display Rating: NEMA 4. ​​
    • Mounting Option: Remote mount with kit, up to 200ft. ​
    • Display: 4.3 inch touch screen display. ​​ Resolution of 480×272 pixels. ​​
  • Material:
    • Remote Mount Display: Powder Coated Die Cast Aluminum. ​
    • Flow Sensor: Wetted metal components: 316 Stainless Steel, Sensor head: XAREC. ​
    • Factory Provided Cable (Sensor to Remote Display): Up to 200’ of three twisted pairs, 22 gauge conductors with individual shields, PVC jacketed, suitable for direct burial with ½” NPT conduit connections or strain relief fitting. ​
  • Programming:
    • Available Options: Menu-driven user interface via touchscreen, PC user interface via micro USB and downloadable software. ​
  • Electrical Connections:
    • Input Power: Removable orange terminal blocks for use with 18-22 AWG. ​​
    • I/O Signals: Removable green terminal blocks for use with 18-22 AWG. ​
    • RS485: Removable green terminal blocks for use with 18-22 AWG. ​​
    • IP: RJ45 connector. ​
  • Communication Protocols:
    • BACnet MS/TP, BACnet UDP/IP, MODBUS RTU, MODBUS TCP/IP. ​​
  • Network Configuration & Addressing: ​
    • BACnet MS/TP: Baud Rates: 9600, 19200, 38400, 57600, or 76800 (Default: 38400), Device Address Range: 1 – 127 (Default: 017), Device Instance Range: 1 – 4,194,302 (Default: 57017), Max master: 1-127. ​
    • BACnet UDP/IP: IPV4 Address: Programmable (Default: 192.168.1.24), Instance Number: 1 – 4,194,302 (Default: 57017), Subnet Mask: Programmable (Default: 255.255.255.0), Gateway Address: Programmable, UDP port: Programmable (Default: 47808). ​
    • MODBUS RTU: MODBUS Address Range: 1- 247 (Default: 017), Baud Rates: 9600, 19200, 38400, 57600, or 76800 (Default: 38400), Data format: 8 bit, Stop bits: 1, Parity: None, Odd, or Even (Default: None), Byte Order: ABCD. ​
    • MODBUS TCP/IP: IPV4 Address: Programmable (Default: 192.168.1.24), Subnet Mask: Programmable (Default: 255.255.255.0), Gateway Address: Programmable, Port: Programmable (Default: 502). ​
  • Approvals:
    • CE: IEC 61000-6-2 Power-Frequency Magnetic Field, Radiated Immunity and Electrostatic Discharge, IEC 61000-6-4 Radiated Emissions, EN 301 489-17 Radiated Emission, RF Immunity, and Electrostatic Discharge, EN 301 328 Wideband transmission systems. ​
    • UL: UL 50: Standard for Enclosures for Electrical Equipment, UL ANSI/NSF 61 & 372 Drinking Water Safety (SENSOR ONLY), UL 61010-1 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use. ​
    • FCC: Part 15, Subpart B. ​

Please note that the specifications are subject to change without notice. ​

View datasheet or request more information sales@ibc.ie