Distributed I/O over Ethernet
The EasyIO Neo CM-ETH provides Ethernet connectivity for the EasyIO Neo modular I/O range. It supplies power and communication to the connected signal modules and transfers their input and output data to a compatible controller, supervisory system or MQTT broker.
CM-ETH can be integrated into compatible third-party systems through the supported protocol. An existing EasyIO installation is not required, but the connected signal modules must be compatible EasyIO Neo modules. Application control logic runs in the connected controller or supervisory system; CM-ETH provides the I/O interface.
Key features
- Protocol selection: BACnet/IP, Modbus TCP or MQTT, with one protocol mode active at a time.
- Modular I/O: supports up to 10 signal modules, subject to a maximum of 80 physical I/O points.
- Dual Ethernet ports: two 10/100 Mbps RJ45 ports with an internal switch for daisy-chain connections and RSTP ring configurations.
- Network commissioning: device discovery, configuration validation, point monitoring and firmware upgrades through IO Manager 2.0.
- MQTT connectivity: supports an external local or cloud broker, with TLS and mutual TLS options.
- Panel installation: compact DIN rail module with LED status indication.
Compatible Neo signal modules
The signal modules determine the available inputs and outputs. Module quantities must remain within both the 10-module and 80-point limits; an assembly using only 16-point modules can contain a maximum of five signal modules.
| Module | I/O provision | Supported signals |
|---|---|---|
| SM-16UI | 16 universal inputs | Voltage, current, resistance, supported temperature sensors, volt-free contacts and pulse inputs |
| SM-16DI | 16 digital inputs | Volt-free contacts and pulse inputs |
| SM-8AO | 8 analogue outputs | 0–10 V, 2–10 V, 0–20 mA or 4–20 mA |
| SM-8DO | 8 digital outputs | Relay switching, rated 24 V AC/DC, 1 A |
Commissioning and integration
IO Manager 2.0 configures the communication protocol, network settings and signal-module points. It also supports configuration validation, batch operations and EDE or CSV exports for integration workflows.
RSTP is disabled by default. Ring installations require RSTP to be enabled on each applicable device. The user guide specifies approximately 1–3 seconds for communication recovery in an RSTP ring; including an STP-only device changes the ring to STP operation and increases recovery time.
MQTT operation requires an external broker. TLS or mutual TLS connections require the corresponding certificates and, for mutual TLS, a client private key. IO Manager configures the connection; it does not provide the broker.
Technical specifications
| Product code | CM-ETH |
|---|---|
| Communication protocols | BACnet/IP, Modbus TCP or MQTT; one protocol mode active at a time |
| Ethernet ports | 2 × 10/100 Mbps RJ45 ports with an internal switch |
| I/O capacity | Up to 10 compatible signal modules, maximum 80 physical points |
| Power supply | 24 V AC, +20%/−15%, 50/60 Hz, or 24 V DC, +20%/−15% |
| CM-ETH power consumption | Less than 6 VA, excluding connected signal modules |
| Operating temperature | 0–50°C |
| Operating humidity | 10–90% RH, non-condensing |
| Dimensions | 40.8 × 104 × 79 mm |
| Protection rating | IP20 |
Technical downloads
- Communication and Signal Modules – Datasheet (LIT-1901247, revision 2.0, PDF)
- Communication and Signal Modules – Installation Guide (LIT-12014561, revision 2.0, PDF)
- Communication and Signal Modules – User Guide (LIT-12014566, revision 2.0, PDF)
- IO Manager – Installation Guide (LIT-12014568, revision 2.0, PDF)
- IO Manager – User Guide (LIT-12014569, revision 2.0, PDF)
- EasyIO Neo I/O Modules – Product Catalogue 2026–2027 (PDF)
- CM-ETH – Secure Deployment Guide (GPS0076-CE-EN, Rev A, PDF)
- EasyIO Neo Series – MQTT User Guide (LIT-12014602, revision 1.0, PDF)