Fan arrays are often treated as a single air-moving system, but the measurement requirement does not have to stop at one total airflow value.
Where greater visibility is useful, the BMS can be given information about individual fans or fan groups rather than only the combined duty of the complete array.
The interesting specification question is therefore not whether total airflow is right or wrong. It is what level of airflow visibility is useful for the project.
One fan array can provide different levels of airflow visibility
Air Monitor’s FAN IV provides up to four independent measurement channels.
For fan-array applications, Air Monitor states that an individual channel can be assigned to each fan for individual fan tracking. Where multiple fans are controlled by the same VFD, fans can instead be grouped so that a channel represents the combined airflow of that fan group.
This creates three distinct monitoring approaches:
| Monitoring approach | FAN IV configuration | Information available |
|---|---|---|
| Total fan-array airflow | System total across the configured channels | Combined airflow for the complete array |
| Individual fan visibility | One fan assigned to each independent channel | Individual channel airflow plus total system airflow |
| Grouped fan visibility | Multiple fans operating from the same VFD grouped on a channel | Combined airflow for each configured fan group plus total system airflow |
The distinction is particularly useful when reading the FAN IV capacity figures. One transmitter provides up to four independent measurement channels. Up to five fans can be grouped on each channel where the fan-array configuration allows it, giving four fan groups totalling up to 20 fans.
That does not mean 20 independently measured fan values. Independent measurement remains limited to the four available channels.
What airflow information can reach the BMS?
The level of airflow visibility chosen for the fan array can also shape the BMS point strategy.
For BACnet MS/TP integration, the FAN IV documentation identifies separate objects for Flow 1, Flow 2, Flow 3, Flow 4 and Total Flow. Differential pressure, velocity, temperature and atmospheric pressure objects are also available depending on configuration.
The transmitter also provides four configurable analogue outputs. These can be assigned to values including total airflow, individual fan or group airflow, differential pressure, temperature and atmospheric pressure.
BACnet MS/TP and Modbus RTU are available as serial communication options.
This means a fan-array measurement strategy can raise several useful design questions:
- Is total fan-array airflow sufficient for the intended controls strategy?
- Would individual fan visibility provide useful operational information?
- Are groups of fans operating together from a common VFD?
- How many genuinely independent measurement channels are required?
- Which values are useful at BMS level rather than only at the local transmitter?
- Will the project use serial communications, analogue signals or a combination of both?
Channel count changes the level of visibility available
A four-channel transmitter can independently measure up to four fans when one fan is assigned to each channel.
A larger fan array does not necessarily require one measurement channel per fan. Where fans operate together and group-level airflow is sufficient for the application, multiple fans can be grouped on a channel.
The trade-off is visibility. Once several fans are represented by one channel, that channel provides the airflow for the group rather than separate airflow values for every fan within it.
For example, a six-fan array requiring six independently measured airflow values would require more independent measurement capacity than one four-channel FAN IV can provide.
Commissioning distinguishes between channel flow and total flow
The FAN IV includes a field-characterisation function that can be used to adjust its flow calculation where airflow is distorted or to bring the transmitter output into closer correlation with field-measured reference data.
Air Monitor’s documentation makes an important distinction: field characterisation is performed with all fans running, using total airflow rather than individual fan readings. The reference value and FAN IV total are entered into the transmitter and the resulting correction is applied to the total system flow.
Individual fan or group visibility is therefore separate from the way this field-characterisation function is applied.
Where the distinction matters at specification stage
The value of individual, grouped or total airflow measurement depends on the fan-array arrangement and what the client needs to see at BMS level.
Points that may influence the measurement approach include:
- the fan-array arrangement and control strategy;
- whether total, individual-fan or fan-group visibility is useful;
- the number of independent measurement channels available;
- whether fans are independently controlled or grouped on common VFDs;
- the airflow sensing arrangement, including piezo-ring or fan-inlet measurement where applicable;
- the BMS points and communication method required for the project;
- whether analogue outputs are needed alongside serial communications;
- the required flow and differential-pressure ranges; and
- how field verification and commissioning data will be established.
The useful distinction is not simply between more data and less data. It is between the level of visibility that supports the project and measurement detail that may not be needed.
Total airflow may be sufficient. The specification question is whether the project also requires individual fan or fan-group visibility.
Air Monitor FAN IV
The Air Monitor FAN IV Fan Array Transmitter uses up to four pressure-transducer channels for fan and fan-array airflow measurement.
Depending on the application, channels can represent individual fans or fan groups, while total airflow is calculated across the configured system. The transmitter supports BACnet MS/TP or Modbus RTU integration and four configurable analogue outputs.
IBC can assist with FAN IV selection, channel configuration and technical documentation where fan-array measurement requirements are being considered.